Vacuum Interrupter For Load Break Switch TF-12/630-20 (2F55)

Tsanangudzo Pfupi:


Product Detail

Product Tags

anopa

Notes

1. Inosangana kana kudarika magetsi ekutsungirira zvinodiwa zvekirasi E2 ye autoreclosing duty per IEC62271-100 uye GB1984-2003.

2. Hunhu hwakatemerwa huchapihwa pakukumbira.

3. Rated insulation values ​​inoda extemal insulati pa, seSf6, mafuta kana yakasimba dielectric material etc.

Main Technical Specifiation

Rated Voltage

KV

12

Rated Current

A

630

Rated Frequency

Hz

50

Nguva pfupi Simba-frequency Inomira Voltage (1min)

KV

42

Rated mheni Impulse Inomira Voltage(Peak)

KV

75

Yakatemerwa Peak Kutsungirira Ikozvino

THE

50

Rated Short-circuit Kuita Ikozvino

THE

50

Yakatemerwa Yenguva pfupi Withstand Current

THE

20

Rated Duration of Short-circ

S

4

Yakatemerwa Yakavharwa-loop Breaking Current

A

630

Yakatemerwa Kugona kweasina-mutoro Transformer

A

No-load Current of Shanduko

Nesimba re1250kVA

Yakatemerwa Cable-charging Breaking Current

A

10

Rated Transferring Current

A

3150

Misa Yezvikamu Zvinofamba

Kg

0.4

Mechanical Endurance

Nguva

10000

Bata Yakavharwa Simba Nekuda kweBellows uye Atmosphere

N

80±30

Counterforce yeKubata paFull Stroke

N

130±30

Circuit Resistance pa Min.Rated Contact Force

Bata Limit Erosion

mm

3

Kuchengetedza Hupenyu

Makore

20

Mechanical Data YeVacuum Switch Yakashongedzerwa Nevanovhiringidza

Clearance Pakati Open Contacts

mm

9±1

Avhareji Yekuvhura Kumhanya

m/s

1.0±0.2

Avhareji Yokuvhara Kumhanya

m/s

0.6±0.2

Rated Contact Pressure

N

900±200

Bata Bounce Nguva paKuvhara Kushanda

ms

Kunze kweSimultaneity yeKubata Kuvhara uye Kushanda

ms

Maximum Rebound Panguva Yekuvhura

mm


  • Zvakapfuura:
  • Zvinotevera: